Compact I/O module with 4 universal inputs, 4 relay outputs and HOA switches. Built-in heating, cooling and lighting applications let it run small loads on its own. It works as remote I/O over Ethernet using BACnet IP or Modbus TCP/IP. The RS485 port acts as a Modbus TCP/IP to Modbus RTU/ASCII gateway for up to 128 Modbus devices. Configure it over BACnet, Modbus or with iSMA's free iSMA Configurator software.
Specifications
- 4 universal inputs: 20+ temperature sensor types (including 10K Type 2 and Type 3, 20K, 3K, Pt1000 and Ni1000), 0 to 10 V DC, 0 to 20 mA, resistance up to 1000 kΩ, or dry contact
- 4 relay outputs, NO, 3 A @ 230 V AC/30 V DC resistive, 75 VA @ 230 V AC inductive
- Hand-Off-Auto switch on each output
- Built-in heating, cooling and lighting applications for standalone use
- Communication: BACnet IP or Modbus TCP/IP, 1 Ethernet port
- Built-in Modbus TCP/IP to Modbus RTU/ASCII gateway on the RS485 port
- Built-in web server
- Configuration: free iSMA Configurator software; Niagara Framework modules available
- Power: 24 V AC/DC
- Mounting: DIN rail