Pti-C12

More Views

Pti-C12

Product Code: BTR6D-00
Model #: 11050108
$115.53

11050108

Pti-C12

The potential divider is used for dividing analog signals in a range from 0 to 10 V DC or 0 to 20 mA. The input and output signals and the supply are mutually isolated. An input signal (0 to 10 V DC or 0 to 20 mA) can be applied optionally to the potential divider. Independently of the type of signal on the input, a voltage of 0 to 10 V DC or a current of 0 to 20 mA can be measured on the output proportionally to the input signal. In addition, a manual emergency operation level with checkback is integrated. A fix 10 V DC signal can be scanned for anti-frost or similar equipment. An external signal (0 to 10 V DC) can be applied to the LED control input Y. Without external signal, the proportional output signal can be indicated by means of the integrated LED by connecting a bridge between Ua and Y. If a voltage signal is used on input and output, use PT-C12. If a current signal is used on input and output, use PTi-C12.

  • Operating voltage 24 V AC/DC
  • Test voltage / separation 1000 V DC
  • Input / voltage 0 V to 10 V DC
  • Input / current 0 V to 20 mA DC
  • Output / fix voltage 10 V DC / 5 mA, fix
  • Output / proportional voltage 0 to 10 V / max. 10 mA
  • Output / proportional current 0 to 20 mA
  • Output / current load max. 500 Ohm
  • Display Green LED
  • Dimensions (W x H x D) 35 x 68 x 60 mm
  • Weight 78 g
  • Operating temperature range 0 °C to +55 °C
  • Storage temperature range -20 °C to +70 °C
  • Ingress protection for housing / terminal block IP40 / IP20
Description

11050108

Pti-C12

The potential divider is used for dividing analog signals in a range from 0 to 10 V DC or 0 to 20 mA. The input and output signals and the supply are mutually isolated. An input signal (0 to 10 V DC or 0 to 20 mA) can be applied optionally to the potential divider. Independently of the type of signal on the input, a voltage of 0 to 10 V DC or a current of 0 to 20 mA can be measured on the output proportionally to the input signal. In addition, a manual emergency operation level with checkback is integrated. A fix 10 V DC signal can be scanned for anti-frost or similar equipment. An external signal (0 to 10 V DC) can be applied to the LED control input Y. Without external signal, the proportional output signal can be indicated by means of the integrated LED by connecting a bridge between Ua and Y. If a voltage signal is used on input and output, use PT-C12. If a current signal is used on input and output, use PTi-C12.

  • Operating voltage 24 V AC/DC
  • Test voltage / separation 1000 V DC
  • Input / voltage 0 V to 10 V DC
  • Input / current 0 V to 20 mA DC
  • Output / fix voltage 10 V DC / 5 mA, fix
  • Output / proportional voltage 0 to 10 V / max. 10 mA
  • Output / proportional current 0 to 20 mA
  • Output / current load max. 500 Ohm
  • Display Green LED
  • Dimensions (W x H x D) 35 x 68 x 60 mm
  • Weight 78 g
  • Operating temperature range 0 °C to +55 °C
  • Storage temperature range -20 °C to +70 °C
  • Ingress protection for housing / terminal block IP40 / IP20
Additional Information
Additional Information
Product Code BTR6D-00
Model # 11050108
Brand Metz Connect, Inc.
Manufacturer Metz Connect USA, Inc.